2019 No.3
Operation And Maintenance运行与维护
Electric Power System Equipment电力系统装备
LW25-126型SF6断路器保护防跳和机构防跳的比较与选用
沈 海
(国网江苏省电力公司苏州供电分公司,江苏苏州 215600)
[摘 要]断路器防跳回路是二次回路的重要组成部分,然而断路器保护防跳回路与机构防跳回路的配合却不尽完美,本文对LW25-126 型 SF6 断路器保护防跳和机构防跳进行了比较,指出了两者的异同点。
[关键词]断路器;防跳继电器;保护[中图分类号]TM561 [文献标志码]A [文章编号]1001–523X(2019)03–0172–02
Comparison and Selection of Protection and Mechanism Anti-jump of
LW25-126 SF6 Circuit Breaker
Shen Hai
[Abstract]The anti-jump circuit of circuit breaker is an important part of the secondary circuit, but the cooperation between the anti-jump circuit of circuit breaker protection and the anti-jump circuit of mechanism is not perfect. This paper compares the anti-jump protection of LW25-126 SF6 circuit breaker with that of mechanism, and points out the similarities and differences between them.
[Keywords]circuit breaker; jump-proof relay; protection“防跳”是指在手合断路器于故障线路且发生手合开关接点粘连的情况下,防止由于“线路保护动作跳闸”与“手合开关接点粘连”同时发生造成断路器在“合闸”与“跳闸”之间发生“跳跃”的情况。为了防止发生这种跳跃现象造成开关损坏爆炸,所以在线路保护的操作回路和断路器的机构中都加装了防跳回路。这两种防跳原理有什么区别,又是怎样配合和选用的,本文以LW25-126型SF6断路器为典型案例来加以说明。
1 断路器微机保护防跳回路
+KM
HBJHBJHJ
LP
D2
S2TBJVS1HYJ1HYJ2
HBJ
TBJTBJV
KKJ
LPTBJ
S3TYJ1TYJ2
TBJ
TQHC
合闸保持-KM
合闸回路已经被断开。这就是 LW25-126型断路器机构“防跳”回路的动作原理。
+KM
电源
远方就地远方就地
T9
11-52TC7
43LR11-52C
DK
52Y52a52Y
88M
R152Y
52Y
63GLX49MX52b
52C
33HBX52b
52T
-KM
合闸回路跳闸回路
52a52a52a52a
TBJV防跳
TJ
保护跳闸跳闸保持
图1 南瑞RCS941A线路保护操作回路
TBJV:防跳继电器;HBJ:合闸保持继电器;
HC:合闸线圈;TQ:跳闸线圈;TBJ:跳闸保持继电器
动作过程:当手合KK开关粘连且发生手合到故障线路上时,微机保护接通跳闸回路(正电源-TJ-TBJ继电器-DL-TQ-负电源),使TBJ继电器带电,TBJ继电器一方面通过自身常开接点自保持,另一方面其另一副常开接点接通防跳回路(KK-TBJV继电器-TBJ-负电源),使TBJV防跳继电器带电。TBJV继电器一方面通过自身常开接点自保持,另一方面其常闭接点可靠地断开合闸回路。这就是 LW25-126型断路器微机保护“防跳”回路的动作原理。2 断路器机构防跳回路
LW 25-126型断路器的操作机构二次回路如图2所示。动作过程:当手合KK开关粘连且发生手合到故障线路上
,则C7一时,不考虑微机保护防跳回路的影响(即短接S2)
直带正电,由于43LR正常置于远方位置,使43LR常闭接点带电,断路器常开接点 52a、52Y 常闭接点起动,52Y 常开接点和电阻R1实现自保持,52Y常闭接点断开合闸回路。也就是说,在发生“手合按钮粘连”的情况下,52Y 的“防跳”功能是由断路器的合闸操作起动的,即“合闸”之后,断路器
3 保护防跳与断路器机构防跳的异同
保护操作回路防跳和断路器机构防跳的相同点在于当手合KK开关粘连且发生手合到故障线路上时,都能实现“防跳”功能。不同点为保护操作回路防跳由跳闸回路启动防跳回路,线路有故障时可靠启动,无故障跳闸时不启动,而断路器机构防跳KK粘连合闸时就可启动。4 保护防跳与断路器机构防跳的选用
由于保护防跳与断路器机构防跳的启动条件不同,所以两种回路不能混用,不然就会形成很多寄生回路,造成跳闸和合闸回路逻辑混乱。现举例如下。
如图3为保护操作回路与断路器机构配合回路,如果两种防跳回路都采用,当正常KK开关合闸但其接点不粘连,断路器合闸后,因为KK接点不粘连,所以断路器机构的防跳回路不会接通。由于断路器的常开辅助触点闭合,使图3中跳闸回路接通。TWJ跳闸位置继电器和52Y机构防跳继电器由于电阻R5-R7分压,使其达不到动作电压,但LD绿灯却有足够的电流点亮,从而造成了TWJ跳闸位置继电器不动作而LD绿灯亮的情况。
由以上分析可知,保护的防跳回路与断路器的机构防跳回路之间存在寄生回路,不能简单的同时使用。为此采取了反措:每台断路器只能保留一个防跳回路。一般采取保留保护操作回路的防跳回路,也有采用断路器本身机构防跳回路的。
图2 LW25-126断路器机构回路
43LR:断路器机构远近控开关;11-52C:机构手合按钮;
11-52T:机构手跳按钮;52Y:机构防跳继电器;52a:断路器常开接点;52b:断路器长闭接点;
88M:储能电机接触器;49MX:电动机辅助继电器(反映电机过流过热故障);33HBX:辅助继电器(弹簧未储能时带电常闭接点打开);63GLX:SF6低气压闭锁继电器
172丨电力系统装备 2019.3
电力系统装备
Electric Power System EquipmentOperation And Maintenance运行与维护
2019年第3期
2019 No.3
浅析华能金陵电厂2号发电机端部黄粉处理相关问题
周家根
(华能金陵发电有限公司,江苏南京 210034)
[摘 要]大型汽轮发电机定子端部绕组及其结构的安全性与可靠性对整个机组的安全稳定运行起着十分重要的作用,发电机膛内的强电磁力引起的的振动可能导致黄粉堆积问题,对发电机的平稳运行有着很大的影响,严重情况下更可能会导致一系列事故,本文针对金陵电厂#2发电机端部黄粉问题的发现与处理进行了总结,对同类型机组端部绕组振动问题的处理提供了参考。
[关键词]汽轮发电机;振动;黄粉;平稳运行[中图分类号]TM621.3 [文献标志码]A [文章编号]1001–523X(2019)03–0173–02
Analysis on the Problems Related to the Treatment of Yellow Powder at the End of
No.2 Generator of Huaneng Jinling Power Plant
Zhou Jia-gen
[Abstract]The safety and reliability of the stator end windings and their structures of large steam turbine generators play an important role in the safe and stable operation of the whole unit. The vibration caused by the strong electromagnetic force in the generator 可能 may lead to the accumulation of yellow powder. The problem has a great impact on the smooth operation of the generator. In severe cases, it may lead to a series of accidents. This paper summarizes the discovery and treatment of the yellow powder problem at the end of the generator #2 of Jinling Power Plant. The treatment of the winding vibration problem provides a reference.
[Keywords]steam turbine generator; vibration; yellow powder; smooth operation1 背景
华能金陵电厂拥有两台1030 MW发电机,端部固有频率在两倍频范围内,此次发生的黄粉问题是2号发电机,初步判断绑绳表面覆盖的黄粉极有可能是运行中的长期振动磨损导致。
在2号机组检修过程中发现的情况如下。
(1)2号发电机靠励磁机侧(以下简称励侧)端部发现少量粉末,经化验分析可得部分为绝缘盒漆皮掉落产生,部分为黄粉。经过仔细检查并未发现靠汽轮机侧(以下简称汽侧)端部内支撑环上的固定绑扎带有松动现象以及裂纹产生。(2)2号发电机汽端、励端支架总体情况良好,汽侧5点钟方向有一个短支撑架的紧固螺丝上方存在积粉情况,用内六角紧固该螺丝并无松动情况。
(3)使用内窥镜检查转子进风口护环内侧靠近线棒处存在大量粉末,同时有类似胶质熔化痕迹。
2 发电机定子端区电磁特性与绕组动力学问题研究概述
大型汽轮发电机端部绕组是一组庞大的载电流体,运行时这种载流导体在端区强大电磁场环境中将产生很大的电磁
力,进而产生相应的振动。若发电机设计、制造工艺、安装及运行中存在问题,会带来安全生产的隐患,严重时会导致事故的发生。
2.1 端部绕组电磁力的研究
发电机的单机容量与定子端部绕组所受的电磁力成正比。金陵电厂两台发电机组均为1030 MW机组,大容量下产生的电磁力也相应较大,运行时,强电磁力作用下绕组的振动也更大。
2.2 端部绕组的振动问题
在转子进风口护环内侧靠近线棒处发现的大量粉末,检查后发现该粉末为护环内绝缘垫块本身磨损掉落,因护环内的绝缘垫块为半松半紧状态,绝缘垫块在运行中因离心力的作用相互磨损产生。通过查询对比得知同类机组也发现过类似情况,产生的粉末情况比金陵电厂严重,并不妨碍运行。3 处理工艺
针对上述情况制定具体方案,对2号发电机进行处理:(1)可采用小型吸尘器对表面黄粉堆积处进行预先处理,吸出裂缝处残留黄粉,后采用酒精或带电清洗剂对所有黄粉
微机操作箱断路器机构箱
图3 保护操作回路与断路器机构配合回路
(1)采用微机保护操作回路防跳回路
由于只保留微机保护操作回路的防跳回路,所以只需要屏蔽掉断路器机构的防跳回路,此时只需要拆掉图3中断路器机构的防跳回路,即图3 X处断开,就断开了两种防跳回路的寄生回路,不会造成正常KK合闸不粘连情况下LD灯还点亮
的情况发生。
(2)采用断路器机构的防跳回路
如果屏蔽微机保护操作回路的防跳回路而保留断路器本身机构的防跳回路,那么只需要短接图1中的TBJV防跳继电器的常闭接点,即短接S2。5 结语
断路器的这两种防跳回路是断路器二次回路最重要的组成部分,其可靠程度关系着电力系统的安全运行。在实际运行中无论使用哪种防跳回路,只保留其中一种防跳回路,这样就避免了两者之间寄生回路的产生。
参考文献
[1] 南瑞继保RCS941A保护说明书[S].[2] LW25-126(145)说明书[S].
2019.3 电力系统装备丨173
因篇幅问题不能全部显示,请点此查看更多更全内容